Bimetallic IPC Connector Insulation Piercing Connector

IPC Connector

Origin: China

Type: PCT13C Series

*Copper tinned teeth can be used for copper or aluminum conductor.

Aluminum teeth can be used for aluminum conductor.

Sample: Free supply

OEM/ODM: Can be customized

Send Inquiry
Category:
Description

Description

Bimetallic IPC Connector Insulation Piercing Connector

Bimetallic IPC connector insulation piercing connector is used to tap or splice the aerial bundle cable.It is mainly composed of an insulating shell, a puncture blade, a waterproof rubber pad, and a torque bolt. Copper tinned puncture blade can be connect the copper conductor or aluminum conductor,the aluminum blade can be connect the aluminum conductor.

Bimetallic IPC connector

 

 

 

Models PCT13C 95/10 PCT13CB 95/10
Main Line(mm2) 6-95 6-95
Service Line (mm2) 1.5-10 (B) 1.5-10
Bolt No. 1 1
Torque (Nm) 10NM 10NM
Remarks ISO to ISO ISO to Bare

IPC Connector

Models PCT13C 70/35 PCT13C 95/50 PCT13C 120/25 PCT13C 150/50 PCT13C 185/35 PCT13CB 70/35 PCT13CB 95/50
Main Line(mm2) 16-70 16-95 25-120 50-150 50-185 16-70 16-95
Service Line (mm2) 4-35 4-50 6-25 4-50 6-35 (B)4-35 (B)4-50
Bolt No. 1 1 1 1 1 1 1
Torque (Nm) 15NM 17NM 17NM 17NM 17NM 15NM 17NM
Remarks ISO to ISO ISO to ISO ISO to ISO ISO to ISO ISO to ISO ISO to Bare ISO to Bare

Insulation Piercing Connector

Models PCT13C 95/95 PCT13C 150/150 PCT13CB 95/95 PCT13CB 150/150
Main Line(mm2) 16-95 16-150 16-95 16-150
Service Line (mm2) 16-95 16-150 (B)16-95 (B)16-150
Bolt No. 1 1 1 1
Torque (Nm) 17-23NM 23NM 23NM 23NM
Remarks ISO to ISO ISO to ISO ISO to Bare ISO to Bare

Installation

When making a cable branch connection, insert the branch cable into the branch cap and determine the position of the main line branch, use a socket wrench to tighten the torque nut on the clamp. As the torque nut is tightened, the upper and lower two insulators with piercing blades hidden in the clamp Gradually close, at the same time, the arc-shaped sealing rubber pad wrapped around the piercing blade gradually adheres to the cable insulation layer, and the piercing blade also begins to pierce the cable insulation layer and metal conductors. When the sealing degree of the sealing rubber gasket and the insulating grease and the contact between the piercing blade and the metal body reach the best effect, the torque nut will automatically fall off. At this time, the installation is completed and the contact point sealing and electrical effect reach the best.

Insulated Piercing Connector Catalogue download